Standby generator coolant heater

Sized on coolant volume, not on kVA

A standby generator coolant heater holds the engine coolant at 40 to 55 °C while the set waits, so the engine starts easily and takes load the moment the mains fails. We size it on the coolant volume of the engine, not on the kVA rating of the alternator.

Sets with 150 to 500 litres of coolant take a POWERHEAT 12 – 26 kW on 400 to 690 V three phase; smaller sets take a TopStart, FlowStart or Zerostart. Every unit is connected in bypass, so the cooling system of the engine itself is not modified.

Diesel engine of a standby generator prepared for coolant preheating
0,5 – 26kW
Four series, one supplier
150 – 500L
Coolant volume on POWERHEAT
400 – 690V
Three phase options
40 – 55°C
Typical standby temperature
Sized per engineSend the engine make and model and we check the coolant volume.Contact Us →
Sizing

Sizing a standby generator coolant heater

The coolant volume of the engine decides the size, not the kVA rating. Where the set stands and the target coolant temperature then fix the exact output.

POWERHEAT 12 to 26 kW coolant heater for large standby sets
Sizing by coolant volume
Up to 30 LZerostart / FlowStart
30 – 150 LTopStart 1 – 9 kW
150 – 500 LPOWERHEAT 12 – 26 kW
01
Why not size on kVA

Turbocharged engines now deliver far more power per litre of coolant than older blocks, so two 500 kVA sets can carry very different volumes. The heater warms the coolant, and that is a figure in litres. Send the engine make and model and we check the volume against the engine data.

02
Ambient conditions

A set in an outdoor container or a rooftop enclosure loses heat all the time; the same set in a heated plant room hardly does. For exposed sets we move up a step in output.

03
Target temperature

The engine builder specifies the standby coolant temperature, usually between 40 and 55 °C. TopStart is adjustable from 0 to 80 °C and POWERHEAT from 20 to 90 °C; Zerostart and FlowStart have fixed thermostats.

04
Undersized or oversized

Because the heater works in bypass, an undersized unit does not harm the engine: it only takes longer to reach the set point. An oversized unit gets there sooner and then switches off on its thermostat.

Duty

Why a standby set needs preheating

A standby set stands still for weeks and must then run up and accept full load within seconds of a mains failure. Started cold, a large diesel does that with thick oil and tight clearances, which is where most start-up wear happens. Held at 40 – 55 °C, it takes load straight away and with less wear.

01
Where it applies

Data centre and hospital sets, fire pump engines, rail power packs, offshore emergency sets and containerised mobile gensets. They share the same duty: long standstill, then full output at once.

02
The weekly test run

A short test run on a cold engine often ends before it reaches operating temperature, which leaves condensation and unburned fuel behind. On a preheated engine the same run starts at 40 – 55 °C.

03
Wear and maintenance

Fewer cold starts mean less wear on bearings and liners and a longer interval between major overhauls. A warm engine also starts more cleanly, with fewer harmful emissions in the first minutes.

04
When a heater is not needed

A prime power set that runs continuously stays warm on its own, and so does an engine in a room kept at its target temperature. In those cases we tell you a heater adds nothing.

Coolant heater connected in bypass to the cooling circuit of a standby engine
Standby duty
Sectors we supply
Data centre standby
Hospital and life safety
Fire pump sets
Rail power packs
Offshore emergency sets
Site and event power
Before you order

What site teams ask us first

"We already test it weekly"

A short run on a cold engine rarely reaches operating temperature and leaves condensation behind. A preheated engine starts that run at 40 – 55 °C.

"It is another thing to maintain"

Zerostart has no moving parts at all. On pumped units the pump and the thermostats are the only wear items, and POWERHEAT is sealed to IP67.

"Will it fit our engine?"

The heater is fitted in bypass with two hoses and a bracket, so the engine is not modified. We fit Caterpillar, Cummins, MTU, Perkins, Volvo Penta, MAN and other makes.

Send the engine type and coolant volume
Our experienced team replies with the unit that fits and its datasheet.
Supply

Single phase or three phase on a standby set

Up to 3 kW a heater runs on 230 V single phase. Larger TopStart units and all POWERHEAT units run on three phase, POWERHEAT on 400 to 690 V. Each unit is built for one voltage, so we confirm the supply at the set before we name the unit.

TopStart coolant heater for standby sets on 230 to 690 V
Mid range sets
TopStart
1 – 9 kW
Coolant volume30 – 150 L
Voltage230 – 690 V
Thermostat0 – 80 °C adjustable
Connections3/4"
POWERHEAT coolant heater for large standby generator sets
Our own line
Large sets
POWERHEAT
12 – 26 kW
Coolant volume150 – 500 L
Voltage400 / 440 / 480 / 690 V
Thermostat20 – 90 °C adjustable
Connections1" · IP67
01
Where the supply comes from

The heater is usually fed from the board that also feeds the battery charger and the enclosure lighting. That board must stay live while the set is not running. Anything above 230 V is connected by an electrician.

02
Control on three phase units

A three phase TopStart has its contactor and a transformer for the single phase pump and thermostats in a separate housing. POWERHEAT has the transformer, contactor and both thermostats built in, so it connects directly to the three phase supply.

Technical documents

Datasheets as open PDF downloads

Voltage, output, thermostat range, connections, weight and dimensions per model.

Zerostart
0,75 – 2,25 kW
FlowStart
0,5 – 2 kW
TopStart 1 – 3 kW
1 – 3 kW
TopStart 4 – 12 kW
4 – 12 kW
POWERHEAT 12 – 18 kW
12 – 18 kW
POWERHEAT 20 – 26 kW
20 – 26 kW
A model that is not listed? Our experienced team sends you the right document.Contact Us →
FAQ

Frequently asked questions about standby generator coolant heaters

01Does the kVA rating decide the heater size?+

No, the coolant volume does. Two sets with the same kVA rating can carry very different volumes, depending on the engine. The volume is in the engine manual; send us the make and model and we check it.

02Can a coolant heater be fitted to an existing standby set?+

Yes. The heater is connected in bypass: one hose from a low point on the block, one return to the engine. Nothing on the engine itself changes, only a bracket and the hose connections. Drain the coolant to below the tapping point before you start.

03What temperature should the coolant be held at?+

The engine builder specifies it; for most standby diesels it lies between 40 and 55 °C. TopStart is adjustable from 0 to 80 °C and POWERHEAT from 20 to 90 °C. Send us the figure from the manual and we confirm the series.

04Does the heater run all the time?+

Only while the thermostat calls for heat. Once the coolant reaches the set point the element switches off, and it switches on again as the engine cools. How often depends on where the set stands, which is why we ask about the ambient conditions.

05Which unit suits a large data centre or hospital set?+

Sets with 150 to 500 litres of coolant take a POWERHEAT 12 – 26 kW. The housing is the same size from 12 to 26 kW, which helps in a packed plant room or container. Above 500 litres, two or more units are fitted to one engine.

06Immersion heater or bypass tank heater?+

An immersion heater is an element fitted into the engine block; today it is mainly used on small automotive engines. A bypass tank heater sits outside the engine in the coolant circuit. For standby sets we recommend the bypass type: it heats more evenly and can be sized for the full coolant volume.

07Are the heaters CE marked and made in the EU?+

Every unit is CE marked, and UL certified models are also available. About 90 % of what we supply is produced in the EU.

Still a question
Ask the team that sizes the units

Send the engine type, the coolant volume and the voltage on the set. Our experienced team replies with the unit that fits.

Four details and we name the unit

Engine type, coolant volume, available voltage and where the set stands. We reply with the unit that fits and its datasheet.